This Knowledge Base provides clear answers about compressed air monitoring and SUTO iTEC products. Topics include installation, choosing the right instruments, and solving common issues. We update this section regularly with new content. If you cannot find the information you need, please contact us.

Analog output mismatches are typically caused by scaling differences, incorrect signal configuration, or electrical signal issues.

A mismatch between analog output and displayed value usually results from scaling or unit inconsistencies between the sensor and the receiving device.
Possible causes:
  • The analog output range is configured differently from the displayed engineering range.
  • The display shows one unit while the analog output is assigned to another unit or parameter.
  • The PLC or logger interprets the current signal using the wrong scaling.
  • 0–20 mA and 4–20 mA configuration are mixed up.
  • Electrical loading, grounding, or wiring problems distort the signal.
Technically correct checks:
  • Check which parameter and range are assigned to the analog output.
  • Confirm that both sensor and receiving device use the same engineering units and span.
  • Measure the actual loop current with a calibrated multimeter.
  • Verify the burden resistance and input type of the receiving device.
  • Inspect grounding and wiring to exclude signal distortion.