- The analog output range is configured differently from the displayed engineering range.
- The display shows one unit while the analog output is assigned to another unit or parameter.
- The PLC or logger interprets the current signal using the wrong scaling.
- 0–20 mA and 4–20 mA configuration are mixed up.
- Electrical loading, grounding, or wiring problems distort the signal.
- Check which parameter and range are assigned to the analog output.
- Confirm that both sensor and receiving device use the same engineering units and span.
- Measure the actual loop current with a calibrated multimeter.
- Verify the burden resistance and input type of the receiving device.
- Inspect grounding and wiring to exclude signal distortion.